EH5200 Series High Frequency Online UPS (1-3KVA) EH5200 Series High Frequency Online UPS (1-3KVA)

High Frequency Online UPS

EH5200 Series (1-3KVA)

This Online Series is an uninterruptible power supply incorporating conversion technology. It provides perfect protection specifically for computer equipment, communication systems to computerized instruments.The double-conversion principle eliminates all mains power disturbances. A rectifier converts the alternating current from the utility power to direct current. This direct current charges the batteries and powers the inverter. On the basis of this DC voltage. the inverter generates a sinusoidal AC voltage which is constantly powering the loads.Computers and Peripherals are thus powered entirely by the UPS. In the event of power failure, the maintenance-free batteries power the inverter.

Features:
  • Rated power 1KVA to 3KVA;
  • Pure Sine wave output;
  • TRANSIENT VOLTAGE SURGE SUPPRESS protect function for FAX、TELEPHONE、MODEM;
  • Machine efficiency greater than 93%, input power factor greater than 0.99, input current harmonics less than 5%;
  • Compatible to generator;
  • Optional SNMP for monitoring.
Where to Buy?

Overview

eh5000-1

LCD/LED Display Information

1. Inverter Output
2. Standby
3. Fault
4. LCD Screen
5. On/mute
6. Select
7. Off/enter


LCD/LED Display Information

1. FAULT INFO
2. LINE INFO
3. BATTERY INFO
4-8. Load/battery capacity info
9. Bypass info
10. INVERTER INFO

eh5000-2

eh5000-3

Figure 1 Back Panel Information

1. RS232
2. Breaker
3. AC Input Socket
4. Intelligent Interface
5. AC Output Socket
6. Surge Protect Socket

ModelH1KH1KSH2KH2KSH3KH3KS
Capacity
VA/W1KVA/0.9KW2KVA/1.8KW3KVA/2.7KW
Input
Voltage RangeFull Load:160±50%VAC~300±50%VAC;Half Load:110±50%VAC~300±50%VAC
Frequency Range40-70Hz
PhaseSingle phase two wire+ground wire
Distortion<5%
Power factor0.99
  Generator inputsupport
Output
Voltage220 (1±1%)VAC
Frequency (same frequency mode)47~53Hz/57~63Hz
Power Factor0.9
Frequency (battery mode)50±0.25Hz or 60±0.25Hz
Crest ratio03:01
Harmonic distortion≤3%THD (Linear load)
≤6%THD (Nonlinear load)
Output waveformPure Sine Wave
SocketUniversal socket *2Universal socket *4Universal socket *3+Terminal block
Over Load100%-110%: warning sound;
110%-130%:Automatically turns off after 1 minute, or switch to bypass mode when input correct;
>130%:Turn off immediately, or switch to bypass mode when the input correct
Efficiency
Charging Mode85%88%
Battery Mode83%85%
Battery
Battery Type12V/7AH/12V/7AH/12V/7AH/
Battery Number368
Equipment time (full load)>5mins>5mins>5mins
Charging Time(90%)8h8h8h
Charge battery (max)1.0A4.01.0A4.01.0A4.0
Rated charging voltage41.0±1%VDC82.1±1%VDC109.4±1%VDC
Temperature detectionsupport
Conversion time
Utility to Battery0ms
Inverter to bypass4ms
Utility Priority Modesupport
Warning Alarm
Battery Modealarm every 4 seconds
Low Poweralarm  every one second
Over Loadalarm  2 every second
Faultcontinuous alarm
Shape
Dimension (D*W*H) mm350*145*220425*190*320
Net weight(Kg)12724112912
Connector
Micro RS-232Windows,Linux,Sun Solaris,IBM Aix,Compaq True64,SGIRIX,FreeBSD,HP-UX and MAC
USB(Optional)Windows & MAC
Rabbet(Optional)SNMP/AS400 Relay Card/Rs485
EPO(Optional)Support emergency shutdown