Product Category
Power Inverter- EP1000 series 500VA-2KVA Inverter (LED/LCD)
- EP2000 series 300W-1500W Sinewave Inverter
- EP2000 series 5KW-10KW Sinewave Inverter (LCD)
- EP2000 series 1KW-4KW Sinewave Inverter (LCD)
- EP2000 series 12KW-16KW Sinewave Inverter (LCD)
- EP3000 Series 1K-4KW Sinewave Inverter/charger AC120V (LCD)
- EP3000 Series 1K-3KW Sinewave Inverter/charger AC230V (LCD)
- EP3000 Series 4KW-6KW Sinewave Inverter/charger AC230V (LCD)
- EP3000 Series 1KW-6KW SOLAR Inverter
- EP3000 Series 1KW-6KW power Inverter(LED)
- EP8000 series 500-5000VA Communications inverter
OffLine UPS- EA1000 series 500/650/800/1000VA UPS
- EA1150 Series 500/600/650VA UPS
Line Interactive UPS- EW2000 Series 500VA-1000VA UPS
- EW2110 Series 1200VA-1500VA LCD UPS
- EW2000 Series 1200VA-1500VA UPS
- EW2110 Series 500VA-1KVA LCD UPS
- EW2150 Series 500VA-1500VA Sine wave UPS
- EW2150 Series 1000VA-6000VA Sine wave UPS
On-Line UPS- EH5000 Series H1K/2K/3KVA UPS
- EH6000 Series H1K/2K/3KVA LCD UPS
- EH5000 Series H6KVA/10KVA UPS
- EH5110 Series R1kVA-6kVA RACK UPS
- EH5000 Series 3H10KS/15KS/20KS UPS
- EH9115 Series 1 Phase Low frequency UPS 2-15KVA
- EH9115 Series 3 Phase Low frequency UPS 10-80KVA
- EH9115 Series 3 Phase Low frequency UPS 100-160KVA
Voltage Regulators - EVS Series 500/800/1200VA AVR
- SVC Series 1KVA-20KVA voltage regulator
VRLA Battery- Gel Series VRLA Battery
- Electric Vehicle Series battery
- General Series VRLA Battery
- Deep Cycle Seris Battery
- GFM series VRLA Battery
- Solar Series VRLA Battery
- Front Terminal Serials Battery
Pure sine wave output,can be used with ,differe domestic applianecTV,refrigerator,fan, air conditioner,induction cooker,micro-wave over etc. Also applied in the field of industrial process controls, battery charging requirements, personal computers, telecommunications, graphics displays, plating and gold recovery industries and wherever required in the commercial, telecoms, mining or industrial markets. Commercial Solar, Recreational Vehicles.
Extremely low return noise and no disturbance to talking quality.
Special charging system design for better protection of battery life.
Short circuit, overload, overload, over voltage and low battery protection.
Superior performance from CPU control technology.
Compatible with generators and suitable for harsh environment where power voltage is extremely unstable.
Which satisfy the power supply for different back up time.
Use-friendly interface, LCD digital display and computer screen display of inverter operation status.
MODEL
PT12KW
PT15KW/PT16KW
OUTPUT
Power Levels crated at
12KW
15KW;16KW
Output Voltage
220v±20%
220v±20%
Voltage Waveform
Pure Sine wave
Crest Factor
3:1
Output Frequency
Auto Select for 50/60Hz
(Synchronized to Mains)
47Hz ~ 55Hz for 50Hz nominal
56Hz ~ 65Hz for 60Hz nominal
Regulation (Nominal)
±10% typical of nominal voltage
Regulation
±3% of selected output voltage
(Battery mode)
remote set-up software
Transfer time
Blackout 3ms typical
Brownout 1ms typical
Battery mode to Normal mode 5ms typical
Over current protection
Over load alarm level 100% ~ 120%
Over load shutdown level 120% ~ 190%
(Adjustable by using the remote set-up software)
INPUT
Nominal Voltage
200V/220V/230V/240V Selectable
200V/220V/230V/240V Selectable
Input Frequency
47Hz ~ 65Hz, 50/60Hz auto-sensing
Efficiency (Normal mode)
97%
Noise Filtering
Full time EMI/RFI filtering
Voltage Range
145V-275V
145V-275V
BATTERY
Battery type
Lead-Acid 50Ah to 500Ah (Recommended)
Lead-Acid 50Ah to 500Ah (Recommended)
Voltage
12KW: 192Vdc
15KW: 192Vdc
16KW:192Vdc
Typical backup time
No Limit
Charging method
Quick charging when battery is not fully charged,
trickle charging when battery is 90% fully charged.
Maximum charging
current25A
25A
Average charging
Quick charging mode:14V maximum.
voltage for each battery
Trickle charging mode:13.5V (adjustable with the remote set-up software)
Protection
Over current protection & Over charging voltage protection (SCR control)
Thermal protection (CPU control)
When temperature inside the unit is over 45 °C, charger will stop charging for 2 minutes followed by an 2 minutes charging. The cycle will be repeate
Monitoring
Smart monitoring & warning for failed battery or open-circuit battery.
Auto-detection each time when power on or every 6 days.
COMMUNICATIONS & MANAGEMENT
Standard Interface port
UPSilon2000 compatible; optional for RS232 .
Control panel
LCD or LED Selectable
Audible alarm
Alarm on battery:Low battery & Battery over voltage
Alarm on abnormal operation:Over load, Short-circuit, & Over heat
Green mode function
1% to 14% of full load (adjustable by using the remote set-up software)
(Auto-shut-off in blackout)
The default setting is OFF.
Cooling fan control
Auto on / off, controlled by temperature & operation mode
ENVIRONMENTAL AND SAFETY
Operating Temperature
Up to 1500 meters:0°Cto 40°C
Transit/storage Temp.
15°C below zero to 55°C
Relative Humidity
5 - 95% non condensing
Operating Altitude
0 ~ 3000 meters
PHYSICAL
Appearance
product size(mm)
396*640*1100
Net Weight(Kg)
12KW: 138.0kgs; 15KW: 142.0kgs; 16KW: 171.0kgs
Carton Gross Weight
12KW: 158.0kgs, 15KW: 162.0kgs; 16KW: 196.0kgs
shipping size
700*660*1280
EP2000 series is packed with features and it is one of the most advanced inverter/chargers in the market today. It features premium sine wave output with high surge capability and temperature compensated, power factor corrected, multi-stage charging to meet power needs of demanding loads including inductive motor loads.