Product Category
Power Inverter- EP1000 series 500VA-2KVA Inverter (LED/LCD)
- EP2000 series 300W-1500W Sinewave Inverter
- EP2000 series 5KW-10KW Sinewave Inverter (LCD)
- EP2000 series 1KW-4KW Sinewave Inverter (LCD)
- EP2000 series 12KW-16KW Sinewave Inverter (LCD)
- EP3000 Series 1K-4KW Sinewave Inverter/charger AC120V (LCD)
- EP3000 Series 1K-3KW Sinewave Inverter/charger AC230V (LCD)
- EP3000 Series 4KW-6KW Sinewave Inverter/charger AC230V (LCD)
- EP3000 Series 1KW-6KW SOLAR Inverter
- EP3000 Series 1KW-6KW power Inverter(LED)
- EP8000 series 500-5000VA Communications inverter
OffLine UPS- EA1000 series 500/650/800/1000VA UPS
- EA1150 Series 500/600/650VA UPS
Line Interactive UPS- EW2000 Series 500VA-1000VA UPS
- EW2110 Series 1200VA-1500VA LCD UPS
- EW2000 Series 1200VA-1500VA UPS
- EW2110 Series 500VA-1KVA LCD UPS
- EW2150 Series 500VA-1500VA Sine wave UPS
- EW2150 Series 1000VA-6000VA Sine wave UPS
On-Line UPS- EH5000 Series H1K/2K/3KVA UPS
- EH6000 Series H1K/2K/3KVA LCD UPS
- EH5000 Series H6KVA/10KVA UPS
- EH5110 Series R1kVA-6kVA RACK UPS
- EH5000 Series 3H10KS/15KS/20KS UPS
- EH9115 Series 1 Phase Low frequency UPS 2-15KVA
- EH9115 Series 3 Phase Low frequency UPS 10-80KVA
- EH9115 Series 3 Phase Low frequency UPS 100-160KVA
Voltage Regulators - EVS Series 500/800/1200VA AVR
- SVC Series 1KVA-20KVA voltage regulator
VRLA Battery- Gel Series VRLA Battery
- Electric Vehicle Series battery
- General Series VRLA Battery
- Deep Cycle Seris Battery
- GFM series VRLA Battery
- Solar Series VRLA Battery
- Front Terminal Serials Battery
EH 9115 series provides maximum protection for vital ‘mission-critical' networks, security applications (electro-medical) and industrial applications thanks to its outstanding mechanical and electrical design. The UPS has an extremely outstanding mechanical and electrical design: isolation transformer on the inverter, high short-circuit current and sinusoidal absorption with low THDi.
High accuracy and reliability due to the double DSP control system
low power consumption up to 94%
cold start directly and smart operation for users.
simple to install:capability to install the UPS into any distribution system (neutral not required on rectifier input)
capability of regulating the output voltage (to offset voltage drops down long cable runs)
built-in automatic and manual battery test feature, battery deep discharge protection and temperature compensating charger
back-feed protection: to avoid energy feeding back into the mains supply should a fault occur
reliable, filtered, stabilized and regulated sine wave output (double conversion on-line technology )with filters for atmospheric
disturbance suppression- high reliability, full microprocessor control with no-break static and manual bypasses,extremely high short-circuit
current to ensure compatibility with the most difficult transformer applications (lighting, drives and industrial processes) and an isolation
transformer on the inverter output- maximum reliability and power availability- high level diagnostics: event log with messages, status,
measurements and alarms - available from the built-in LCD in several languages
| MODEL | EH9115-10K | EH9115-20K | EH9115-30K | EH9115-40K | EH9115-60K | EH9115-80K | |
| CAPACITY | 10KVA/8KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | 60KVA/48KW | 80KVA/64KW | |
| INPUT | |||||||
| Voltage | 380/400/415 Vac±20%,3 Phase +N (3 phase and 4 wire) | ||||||
| Input Frequency | 50/60 Hz ±10% | ||||||
| Power Factor | >=0.95 | ||||||
| phase | 3phase | ||||||
| Input voltage protection | Electronic Input out of tolerant protection |
||||||
| OUTPUT | |||||||
| AC Voltage Regulation (Batt.Mode) | 380/400/415 Vac ±1%,3 Phase +N | ||||||
| Voltage tolerant | (balanced load:+/- %1)(unbalanced:+/- %2)(full load:+/-%5) | ||||||
| Voltage regulation time | After full load: 25 ms | ||||||
| Frequency Range | 50Hz (60Hz special product) | ||||||
| Frequency tolerant | (synchron:+/-%2) (free running:+/-%0,2) | ||||||
| Efficiency (100% load) | >85% | >90% | |||||
| Harmonic Distortion | <=3% THD (Linear Load),<=5% THD(Non Linear Load) | ||||||
| Transfer Time | AC to DC | Zero | |||||
| Inverter to Bypass | 4 ms (Typical) | ||||||
| Waveform (Batt. Mode) | Pure Sine Wave | ||||||
| Crest faktor | 3:1 | ||||||
| BATTERY | |||||||
| Battery Type & Numbers | Maintenance free lead-acid batteries / 12V x 32pcs | ||||||
| charge current | 8A | ||||||
| Battery Start | Yes, UPS can be started without AC source. | ||||||
| Battery protection | Automatic circuit breaker | ||||||
| Battery voltage protection | Electronic 3 level alarms | ||||||
| OVERLOAD | |||||||
| Overload protection | (>130-%150 load :60 seconds ) (>%150 load :30 seconds) | ||||||
| Short circuit protection | Electronic protection | ||||||
| Output voltage protection | Electronic out of tolerant protection | ||||||
| PHYSICAL | |||||||
| Dimension, D X W X H (mm) | 600x550x1250 | 780x700x1520 | |||||
| Net Weight (kgs) | 200 | 270 | 330 | 360 | 430 | 500 | |
| OPERATING ENVIRONMENT | |||||||
| Humidity | 0% - 90% (NonLCCondensing) | ||||||
| Temperature | 0 – 40°C | ||||||
| Overtemperature protection | Electronic protection | ||||||
| Noise Level | < 58 dBA (At 1 M) | < 63 dBA (At 1 M) | |||||
| Altitude | <1000 M Above Sea Level | ||||||
| LED,LCD,Buzzer | YES | ||||||
| MANAGEMENT | |||||||
| Remote Control | Dry contact, RS232 | ||||||
| . All specifications mentioned above are subject to change without prior notice. | |||||||
Highest reliability and maximum performance for power sharing and redundancy. Must UPS power systems have been explicitly designed to meet the demands of today's industrial processes and special projects where reliability, availability and serviceability are equally as important as product quality and technical competence.