Product Category
Power Inverter- EP1000 series 500VA-2KVA Inverter (LED/LCD)
- EP2000 series 300W-1500W Sinewave Inverter
- EP2000 series 5KW-10KW Sinewave Inverter (LCD)
- EP2000 series 1KW-4KW Sinewave Inverter (LCD)
- EP2000 series 12KW-16KW Sinewave Inverter (LCD)
- EP3000 Series 1K-4KW Sinewave Inverter/charger AC120V (LCD)
- EP3000 Series 1K-3KW Sinewave Inverter/charger AC230V (LCD)
- EP3000 Series 4KW-6KW Sinewave Inverter/charger AC230V (LCD)
- EP3000 Series 1KW-6KW SOLAR Inverter
- EP3000 Series 1KW-6KW power Inverter(LED)
- EP8000 series 500-5000VA Communications inverter
OffLine UPS- EA1000 series 500/650/800/1000VA UPS
- EA1150 Series 500/600/650VA UPS
Line Interactive UPS- EW2000 Series 500VA-1000VA UPS
- EW2110 Series 1200VA-1500VA LCD UPS
- EW2000 Series 1200VA-1500VA UPS
- EW2110 Series 500VA-1KVA LCD UPS
- EW2150 Series 500VA-1500VA Sine wave UPS
- EW2150 Series 1000VA-6000VA Sine wave UPS
On-Line UPS- EH5000 Series H1K/2K/3KVA UPS
- EH6000 Series H1K/2K/3KVA LCD UPS
- EH5000 Series H6KVA/10KVA UPS
- EH5110 Series R1kVA-6kVA RACK UPS
- EH5000 Series 3H10KS/15KS/20KS UPS
- EH9115 Series 1 Phase Low frequency UPS 2-15KVA
- EH9115 Series 3 Phase Low frequency UPS 10-80KVA
- EH9115 Series 3 Phase Low frequency UPS 100-160KVA
Voltage Regulators - EVS Series 500/800/1200VA AVR
- SVC Series 1KVA-20KVA voltage regulator
VRLA Battery- Gel Series VRLA Battery
- Electric Vehicle Series battery
- General Series VRLA Battery
- Deep Cycle Seris Battery
- GFM series VRLA Battery
- Solar Series VRLA Battery
- Front Terminal Serials Battery
Applied to Servers, Data-Center Critical network devices, Sensitive electronic equipment, Telecom,Departmental servers,smaller lans,workstation,IPC,Small medical equipment,small precision electronic instrument
True on-line double conversion technology with advanced microprocessor control
Wide input voltage range with high frequency technology
Zero transfer time
Protection against all type of power problems
Self test while start of the UPS
Site wiring fault warning
On-battery power-on function
Smart RS232 communication interface
Intelligent slot available
Sealed acid battery,free-maintenance battery
True Regenerative online Uninterruptible Power Supply Design.
As new and innovative technologies have become the backbone of today's businesses, maximum system availability is critical and downtime
is more expensive than ever.Increasingly, businesses need an On Line UPS backup power supply that not only protects against blackouts,
but also virtually eliminates more frequent and subtle power disturbances. Surges, sags, line noise and brownouts can disrupt proper
operation of sensitive equipment. These disturbances may also create unnecessary production, service, and data recovery costs. Must UPS
solves these problems with high quality backup power supply solutions.
A True Regenerative On Line Uninterruptible Power Supply from Must UPS provides the highest level of protection against the widest spectrum of power problems. The incoming AC utility source is converted to a regulated DC voltage. From this DC voltage, a new AC voltage is regenerated, providing continuous, clean, tightly regulated power to your equipment.
Input Power Must Correction
All EH5000 Series UPS Must models include state-of-the-art Input Power must Correction. This greatly reduces the amount of current demanded from your building wiring - system, yielding a highly efficient, "building friendly" UPS.
Microprocessor Control
Must power EH5000 Series UPS incorporates advanced microprocessor technology. This technology makes possible a high level of internal UPS control and management. With the supplied software, all EH5000 Series UPS models support unattended shutdown, management, data logging, and self-diagnostics. The software supports MS Windows® 95, 98, NT, 2000, 2000 Server, ME, XP, Novell Netware® 5 & 6, LINUX and FreeBSD. UPSILON for UNIX supports most popular UNIX platforms and OS versions.
SNMP/HTTP Remote Management Support
Our SNMP/HTTP Agent board provides remote management and monitoring over any Ethernet LAN, WAN or the Internet utilizing a 10BaseT-type connection. The optional SNMP/HTTP agent installs via a port located on the back of every EH5000 Series model.
Extended Battery Ready
All EH5000 Series models have continuous duty inverters and support the addition of optional externalbattery/charger packs. Whether your application requires a few additional minutes or hours, the EH5000 Series is ready.
Frequency Converter Capability
With a factory modification and the addition of an external input transformer, EH5000 Series models can be configured for use as voltage and frequency converters. This makes the EH5000 Series UPS an ideal choice for worldwide power applications.
| Model | H1K(S) | H1.5K(S) | H2K(S) | H3K(S) | |
| CAPACITY | 1000 VA/700 W | 1500 VA/1050 W | 2000 VA/1400 W | 3000 VA/2100 W | |
| INPUT | |||||
| Voltage Range | Low Line Transfer | 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or | |||
| 80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 % | |||||
| (based on load percentage 100% - 80% / 80% - 70% / 70% - 60%/60% -0) | |||||
| LowLine Comeback | 175 VAC ± 5 % or 85 VAC ± 5 % | ||||
| High Line Transfer | 300 VAC ± 5 % or 150 VAC ± 5 % | ||||
|
High Line |
290 VAC ± 5 VAC or 143 VAC ± 3 VAC | ||||
| Frequency Range | 40 Hz ~ 70 Hz | ||||
| Phase | Single phase with ground | ||||
| Power Factor | ≥0.99 @ 220-230 VAC (input voltage) | ||||
| OUTPUT | |||||
| AC Voltage Regulation (Bat. Mode) | ±3% | ||||
| Frequency Range (Synchronized Range) |
47 ~ 53 Hz or 57 Hz ~ 63 Hz | ||||
| Frequency Range (Bat. Mode) | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz | ||||
| Current Crest Ratio | 3:1 | ||||
| Harmonic Distortion | <= 3 % THD (Linear Load) | <= 4 % THD (Linear Load) | |||
| <= 6 % THD(Non-linear Load) | <= 7 % THD(Non-linear Load) | ||||
| Transfer Time | AC to DC | Zero | |||
| Inverter to Bypass | 4 ms (Typical) | ||||
| Waveform (Bat. Mode) | Pure Sine Wave | ||||
| EFFICIENCY | |||||
| To AC Mode | 85% | 88% | |||
| To Battery Mode | 83% | ||||
| BATTERY | |||||
| Standard Model | Battery Type | 12 V / 7 AH | 12 V / 9 AH | 12 V / 7 AH | 12 V / 7 AH |
| Numbers | 3 | 3 | 8 | 8 | |
| Typical Recharge Time | 4 hours recover to 90% capacity | ||||
| Charging Current (max.) | 1.0 A | ||||
| Charging Voltage | 41.0 VDC ± 1% | 102.1 VDC ± 1% | |||
| Long-run Model | Battery Type/Numbers | Depending on the capacity of external batteries | |||
| Charging Current (max.) | 4.5 A | ||||
| Charging Voltage | 41.0 VDC ± 1% | 102.1 VDC ± 1% | |||
| INDICATORS | |||||
| LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | ||||
| ALARM | |||||
| Battery Mode | Sounding every 4 seconds | ||||
| Low Battery | Sounding every second | ||||
| Overload | Sounding twice every second | ||||
| Fault | Continuously sounding | ||||
| PHYSICAL | |||||
| Standard Model | Dimension DXWXH (mm) | 410 X144 X 200 | 455 X 190 X 330 | ||
| Net Weight (KGS) | 12.95 | 14 | 30.25 | 30.5 | |
| Long-run Model | Dimension,DXWXH (mm) | 397 X 145 X 220 | 421 X 190 X 318 | ||
| Net Weight (KGS) | 5.85 | 13.3 | |||
| OPERATING ENVIRONMENT | |||||
| Humidity | 20-90 % RH @ 0- 40°C (non-condensing) | ||||
| Noise Level | Less than 45dB @ 1 Meter | ||||
| MANAGEMENT | |||||
| Smart RS-232/USB | Supports Windows®98/2000/2003/XP/Vista/2008,Windows®7,Linux,and MAC | ||||
| Optional SNMP | Power management from SNMP manager and web browser | ||||
Must EH Series 1K, 2K, 3K UPS are connected through the RS232 communication port to Must Power Management software for power detection and power monitoring, to integrate UPS and the network server into one entity with power status available at any time.